We've had this one for a while, decided to put some power monitoring on it to graph the usage...
The UPS has a metric for each Phase, so for a total output, we have to aggregate the figure. I chose to use Watts in my graphs. The other thing to note is that it requires version 1 of SNMP.
Config below....
$Path is the working directory, needs to exist. $Name is the mrtg name of the instance. $Community is the snmp community (usually public), $host is the hostname/ip of the device. $Title is the friendly name of the instance. Easy as that.
WorkDir:$Path Target[$Name]: enterprises.534.1.4.4.1.4.1&enterprises.534.1.4.4.1.4.1:$Community@$Host:::::1 + enterprises.534.1.4.4.1.4.2&enterprises.534.1.4.4.1.4.2:$Community@$Host:::::1 + enterprises.534.1.4.4.1.4.3&enterprises.534.1.4.4.1.4.3:$Community@$Host:::::1 MaxBytes[$Name]: 36000 Title[$Name]: $Title PageTop[$Name]: <H1>$Title</H1> Options[$Name]: gauge, nopercent, absolute, unknaszero, growright YLegend[$Name]: Watts ShortLegend[$Name]: Watts Legend1[$Name]: Watts Legend2[$Name]: . Legend3[$Name]: Max value per interval on graph Legend4[$Name]: . LegendI[$Name]: True Power LegendO[$Name]: . Colours[$Name]: GREEN#00eb0c,BLUE#0000ff,GRAY#AAAAAA,VIOLET#ff00ff WithPeak[$Name]: ymw